Reference Manual
00809-0100-4530, Rev BA
July 2009
4-11
Rosemount 5300 Series
Non-Intrinsically Safe
Output
With non-intrinsically safe power supply in Non-hazardous installations or
Explosion-proof/Flameproof installations, wire the transmitter as shown in
Figure 4-9.
NOTE!
Make sure that the power supply is off when connecting the transmitter.
Figure 4-9. Wiring for
non-intrinsically safe power
supply (Foundation Fieldbus).
NOTE!
For Explosion Proof/Flameproof installations, make sure the transmitter is
grounded to the internal ground terminal inside the terminal compartment in
accordance with national and local electrical codes.
Power
supply
375 Field Communicator
Rosemount 5300 Series
Radar Transmitter
PC
U
max
=250 V
Fieldbus Modem