Reference Manual
00809-0100-4530, Rev BA
July 2009
7-25
Rosemount 5300 Series
USING THE SIMULATION
MODE
This function can be used to simulate measurements and alarms.
RRM: choose menu option Tools>Simulation Mode:
Figure 7-21. The Simulation
Mode window in RRM.
AMS Suite: Tools>Service>Simulation Mode.
HART Command: [3, 2, 1, 3].
DeltaV:
1. In the DeltaV Explorer, select the desired transmitter icon, and click the
right mouse button on the Transducer 1300 block icon:
2. Choose the Simulation Mode option.
Simulation Mode
TRANSDUCER1300