Reference Manual
00809-0100-4530, Rev BA
July 2009
5-35
Rosemount 5300 Series
15. Choose a pre-defined calculation method based on a tank shape that
corresponds to the actual tank. Choose None if volume calculation is not
desired.
Use Volume Offset if you do not want zero volume and zero level to match
(for example if you want to include the product volume below the zero
level).
The Strapping Table option is used if the actual tank does not match any
of the available options for pre-defined tanks or if a higher calculation
accuracy is desired.
Calculation Method:
F
OUNDATION Fieldbus parameter:
TRANSDUCER 1300>VOL_VOLUME_CALC_METHOD
Diameter:
F
OUNDATION Fieldbus parameter:
TRANSDUCER 1300>VOL_IDEAL_DIAMETER
Tank Length:
F
OUNDATION Fieldbus parameter:
TRANSDUCER 1300>VOL_IDEAL_LENGTH
Volume Offset:
F
OUNDATION Fieldbus parameter:
TRANSDUCER 1300>VOL_VOLUME_OFFSET
See “Volume Configuration” on page 5-7 for more information.