Instruction Manual
IM-106-910Xi, Original Issue
November 2010
1-5
Xi Advanced Electronics
3. The Xi can also transmit HART information wirelessly via a wireless
THUM Adapter, Figure 1-4. The THUM Adapter threads into the Xi
conduit port and converts the 4-20 mA O
2
signal to a wireless protocol.
All other HART information is also transmitted.
In addition to the wireless THUM Adapter, a hard-wire connection of the
4-20 mA signal to the DCS may be used at the same time. More
detailed information regarding the application of the THUM Adapter is
available in Product Data Sheet 00813-0100-4075. Note that the THUM
Adapter may also be used with the Oxymitter, mounted integral to the
probe, or to the Oxymitter remote electronics.
Figure 1-4. Wireless THUM
Adapter
Optional OxyBalance Display and Averaging System
Receives up to eight 4-20 mA signals from individual Xi units. Trends
individual outputs and calculates four programmable averages as additional
4-20 mA outputs. OxyBalance graphic displays are shown in Figure 1-5. See
IM-106-4050, OxyBalance Oxygen Display and Averaging System, for
additional details.
Figure 1-5. OxyBalance
Displays
38890063